Vincenzo Patroni
EMT Modeling and Data-Driven Validation of a Synchronous Motor Load for Power System Restoration.
Rel. Angela Russo, Mario Paolone, Dawn Virginillo. Politecnico di Torino, Corso di laurea magistrale in Ingegneria Elettrica, 2026
Abstract
After a total blackout, a Transmission System Operator (TSO) rebuilds the grid from designated restoration cells: small, low-inertia islands in which the first generating units are stabilized by deliberately energizing large motor loads as ballast. Energizing a multi-megawatt motor on such an island is among the most severe events of the restoration sequence, and assessing the conditions under which it can be performed safely requires dynamic models validated against the behaviour of the real system. This thesis develops a detailed Electromagnetic Transients (EMT) model of the first ballast load of the East Restoration Cell of the Swiss transmission system: a 20.4 MVA synchronous motor-pump unit started by a Load-Commutated Inverter (LCI).
The model covers the complete drive, from the machine and its pump load to an averaged representation of the starting converter, the excitation control, and the measurement and synchronization devices, and is integrated in the EMT model of the cell, where it executes the entire energization sequence autonomously, as in the plant